beautypg.com

Installation installation manual, Condensate drain connections – Takagi T-H3M-IN/OS User Manual

Page 24

background image

24

Page

Installation

Installation Manual

WARNING

Discharge condensate (acidic water) in accordance with all local codes

and common safety practices.

Condensate

drain port

1/2" Condensate

drain tube

Adequate space

Drain

1/2" FPT x 3/8" MPT

(Included with

Neutralizer accessory)

Neutralizer cartridge

(Included with

Neutralizer accessory)
3/8" MPT x 1/2" HB

(Included with

Neutralizer accessory)

Drain

3/8" or 1/2"

Condensate

drain tube

Condensate

drain port

1/2"

FPT x 3/8"

(or 1/2") HB

Adequate space

Case A

Case B

-Condensate Drain Connections-

The water heater is a high efficiency condensing

model

that produces condensate (acidic water)

The

acidic condensate generated in the secondary heat exchanger can be neutralized by the Neutralizer acces-

sory

Case A: If a neutralizer is not required

1 Connect a 1/2” FPT X 3/8” (or 1/2”) HB Adaptor to the condensate drain port at the bottom of the

water heater

2 Connect a condensate drain tube to the 1/2” FPT X 3/8” (or 1/2”) HB Adaptor The manufacturer

recommends the material of the condensate tube be either EPDM or PVC

3 Leave an adequate amount of space between the end of the drain tube and the actual drain, to

facilitate proper drainage

Case B: If a neutralizer is required (installing the Neutralizer assembly)

1 Connect the 1/2” FPT X 3/8” MPT Adaptor to the condensate drain port at the bottom of the water

heater

2 Connect the Neutralizer to the 3/8” MPT connection of the adaptors There is a flow direction indicator

on the neutralizer Please orient the neutralizer in the proper direction

3 Connect a 1/2” drain tube to the other end of neutralizer

4 Leave an adequate amount of space between the end of the drain tube and the actual drain, to

facilitate proper drainage