Dipswitch settings for vent length, Installation installation manual – Takagi T-H3M-IN/OS User Manual
Page 12
12
Page
Installation
Installation Manual
-DIPswitch settings for Vent length-
Vent length
Two-pipe and Single pipe
5 to 50 ft.
(DEFAULT)
No 6 : ON
No 7 : OFF
51 to 100 ft.
No 6 : OFF
No 7 : OFF
OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
ON 1 2 3 4 5 6 7 8 9 10
Vent length
Two-pipe
5 to 20 ft.
(DEFAULT)
No 6 : ON
No 7 : OFF
21 to 40 ft.
No 6 : OFF
No 7 : OFF
41 to 70 ft.
No 6 : ON
No 7 : ON
OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
ON 1 2 3 4 5 6 7 8 9 10
Set DIPswitches shown in the tables below depending on the vent length Only adjust switches with a black
square Black squares indicate the position of the switch
Vent length
Single pipe
5 to 45 ft.
(DEFAULT)
No 6 : ON
No 7 : OFF
46 to 70 ft.
No 6 : OFF
No 7 : OFF
OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
ON 1 2 3 4 5 6 7 8 9 10
Vent length
Single pipe
5 to 6.5 ft.
No 6 : ON
No 7 : ON
OFF
ON 1 2 3 4 5 6 7 8 9 10
2 inch venting
3 inch venting
4 inch venting