beautypg.com

Gas supply and gas pipe sizing, General, Gas connections – Takagi T-H3M-IN/OS User Manual

Page 20

background image

20

Page

Installation

Installation Manual

GAS SUPPLY AND GAS PIPE SIZING

-General-

• The minimum and maximum inlet gas pressures are:

• Inlet gas pressures that fall outside the range of values listed above may adversely affect the

performance of the water heater These pressures are measured when the water heater is in full

operation

• Inlet gas pressure must not exceed the above maximum values; gas pressure above the specified range

will cause dangerous operating conditions and damage to the water heater

• Until testing of the main gas line supply pressure is completed, ensure the gas line to the water heater

is disconnected to avoid any damage to the water heater

-Gas connections-

1 Install a manual gas shutoff valve between the water heater and the gas supply line The gas supply

line shall be checked for leaks using code approved methods

2 When the gas connections are completed, it is necessary to perform a gas leak test either by applying

soapy water to all gas fittings and observing for bubbles or by using a gas leak detection device

• The water heater and its individual shutoff valve must be disconnected from the gas supply

piping system during any pressure testing of that system at test pressures in excess of 1/2 psi

(35 kPa)

• The water heater must be isolated from the gas supply piping system by closing its individual

manual shutoff valve during any pressure testing of the gas supply piping system at test

pressures equal to or less than 1/2 psi (35 kPa)

3 Always purge the gas line of any debris and/or water before connecting to the gas inlet

Size the gas pipe appropriately to supply the necessary volume of gas required

for the water heater using ANSI Z2231/NFPA 54 in the USA or CAN/CSA B1491 in

Canada or local codes Otherwise, flow capabilities and output temperatures will

be limited

NOTICE

Gas type

Inlet gas pressure

Natural Gas

Min 50” WC (124 kPa) – Max 105” WC (261 kPa)

Propane

Min 80” WC (199 kPa) – Max 140” WC (348 kPa)

Check that the type of gas matches the rating plate first.

Ensure that any and all gas regulators used are operating properly and

providing gas pressures within the specified range shown below. Excess gas

inlet pressure may cause serious accidents.

• Conversion of this water heater from natural gas to propane or vice versa will

void all warranty Contact your local distributor to get the correct unit for your

gas type The manufacturer is not liable for any property and/or personal

damage resulting from gas conversions

CAUTION