beautypg.com

Exhaust vent (stainless steel vent), Installation installation manual – Takagi T-H3M-IN/OS User Manual

Page 16

background image

16

Page

Installation

Installation Manual

Vent connections for two-pipe

4" stainless

steel vent

straight pipe

Exhaust vent

collar (Female)

Intake vent collar

(Female)

4" stainless

steel vent

straight pipe

Exhaust vent

collar (Female)

4" stainless

steel vent

straight pipe

Intake vent

collar

(Female)

4" elbow

with bird

screen

1.  Connect a 4" stainless steel vent

straight pipes directly on the

exhaust vent collar of the

water heater

2.  Connect a 4" elbow directly

on the intake vent collar of the

water heater

1.  Connect 4" stainless steel vent

straight pipes directly on the

exhaust/intake vent collar of the

water heater

For details of the optional items, refer to the Installation manual for each Optional item

-Exhaust vent (Stainless steel vent)-

This is a Category IV appliance and must be vented accordingly The vent system must be sealed airtight

All seams and joints without gaskets must be sealed with high heat resistant silicone sealant or UL listed

aluminum adhesive tape having a minimum temperature rating of 160 °F For best results, a vent system

should be as short and straight as possible

• The Indoor model is a Category IV appliance and must be vented accordingly with any 4 inch vent

approved for use with Category III/IV or Special BH type gas vent

The manufacturer recommends the NovaVent (Z-Vent) line However, the following are also UL

listed manufacturers: ProTech Systems Inc (FasNSeal), Metal-Fab Inc, and Heat-Fab Inc (Saf-T

Vent)

Follow the vent pipe manufacturer’s instructions when installing the vent pipe.

• The maximum length of exhaust vent piping must not exceed 100 ft (305 m) (deducting 5 ft (15

m) for each elbow used in the venting system) Do not use more than 5 elbows

• When the horizontal vent run exceeds 5 ft (15 m), support the vent run at 3 ft (09 m) intervals

with overhead hangers

Diameter

Max. No. of Elbows Max. Vertical and Horizontal (Total) Vent Length

4 in (102 mm)

5

100 ft (305 m )

*For each elbow added, deduct 5 ft. (1.5 m) from max. vent length.

No. of Elbows

Max. Vertical or Horizontal Vent Length

0

100 ft (305 m)

1

95 ft (290 m)

2

90 ft (274 m)

3

85 ft (259 m)

4

80 ft (244 m)

5

75 ft (229 m)

Excludes vent terminators, termination elbows, or rain caps

Vent connections for single pipe