HF8 analog current outputs
The maximum permissible cable length, connecting the unit to other devices, is determined by the total
resistance resulting from the addition of the cable resistance and that of the devices connected in series with
the unit. This resistance should not exceed 500 ohms.
Operation of the HF8 does not require all current loops to be closed. Using the ROTRONIC HW4 software,
any unused output of the HF8 can be disabled.