beautypg.com

NORD Drivesystems BU0240 User Manual

Page 25

background image

4 Commissioning

BU 0240 GB

25

Minimal configuration with options
In order to implement completely autonomous operation (i.e. independent of control cables etc.) a
Potentiometer Unit (SK CU4-POT) is required. In combination with an integrated mains unit
(SK CU4-…-24V) a solution can be implemented with only one mains cable (1~ / 3~ according to the
version), and a suitable speed and direction control can be ensured (See connection example below).
This configuration method also provides the possibility of setting the frequency inverter to start automatically
with "Mains On", by changing parameter (P428).

Connection plan and parameterisation of SK CU4-POT, example

 

 

 






SK CU4-POT

Potentio-

meter

0-10

R/0/L

Switch



Frequency inverter
SK 2x5E-...

C

ontro

l term

in

al ba

r

44
40

.
.

21
22
23
24

.
.
.

L1 - L2/N - L3

115/230/400V




24V mains unit
SK CU4-24V-...

L1 - L2/N

115/230/400V

24V=

GND 

10V=

AGND

0-10V

R

L

0-100%

1/3~ 115/230/400V + PE 

Control terminal bar

44 40 44 ... 11 14 12 B1

(br)

(bl) 

(br) 

(blk) 

(gn)

(br) 

(white) 

(bl)

DIP switch settings:

DIP3 = off, DIP4 = on, DIP5 = off

or

recommended
parameter setting, DIP1-8 = off:

P400 [07] = 1 P420 [02] = 2

P420 [01] = 1 P420 [03] = 26

NOTE

An 8-Bit A/D converter is integrated into mains units SK TU4-…-24V and SK CU4-…-24V. This
makes it possible to connect a potentiometer or other analog setpoint source to the mains unit
and to transfer this to the digital input of the frequency inverter via a corresponding pulse signal.