NORD Drivesystems BU0240 User Manual
Page 20
NORDAC SK 200E Manual
20
BU
0240
GB
4.1.2
Configuration
Changes to individual parameters are usually necessary for operation. (Exceptions: see Section 4.1.3 )
Configuration can be carried out to a limited extent via the DIP switches. Configuration by means of
software parameterisation is necessary for more extensive parameter changes.
NOTE
Mixing of DIP switch configuration and (software) parameterisation should be avoided.
4.1.2.1 Parameterisation
The use of a ParameterBox (SK CSX-3H / SK PAR) or NordCon software is necessary to change the
parameters.
Parameter group
Parameter numbers
Functions
Remarks
P201 … P207,
(P208)
Data on motor rating plate
P220, Function 1
Measure stator resistance
Value is written to P208
alternatively
P200
Motor data list
Selection of a 4-pole standard
motor from a list
Motor data
alternatively
P220, Function 2
Motor identification
Complete measurement of a
connected motor
Prerequisite: motor at least 3
power levels less than the
frequency inverter
Basic parameters P102 … P105
Ramp times and frequency
limits
Control terminals
P400, P420
Analog and digital inputs
NOTE
Prior to commissioning, it should be ensured that the frequency inverter is in its default setting
(P523).
If configuration is carried out at a parameter level, the DIP switches must also be set to the
"OFF" position.