3 – AL1 active high
AL2 active low
4 – AL1 active low
AL2 active low
5 – AL1 disabled
AL2 active low
6 – AL1 Active high
AL2 disabled
7 – AL1 active low
AL2 disabled
8 – AL1 disabled
AL2 disabled
00000 – Selects the Hysteresis mode or Band Deviation mode of alarms
0 – AL1 BAND Deviation
AL2 Band Deviation
1 – AL1 Hysteresis
AL2 Band Deviation
2 – AL1 Band Deviation
AL2 Hysteresis
3 – AL1 Hysteresis
AL2 - Hysteresis
4 – No deviation or hysteresis in menu
00000 – Number of reading taken in the alarm zone before the alarm goes off
0 – 1 reading
1 – 2 readings
2 – 4 readings
3 – 8 readings
4 – 16 readings
5 – 32 readings
6 – 64 readings
7 – 128 readings
4. ‘dEU1H’ will appear on the display, enter the setpoint at which you would like ‘alarm 1’ to be
activated. Press the MENU button.
5. ‘dEU2b’ will appear on the display, enter the setpoint at which you would like ‘alarm 2’ to be
activated. Press the MENU button.
Your alarm functions are now ready to use.