TIMER SETTINGS
The timer function of the series LCT216 takes a signal input to start a timing sequence. The
sequence can be paused using the GATE input or reset using RST1 input. Use the below
parameters and timing functions to configure the timer.

Parameter Configuration

PV

SV

FUnC

timE

Sets the controller to function as a timer.

t mode

UP

Sets the display to count up or down.

down

t otmd

Sets the output timing functions. See the timing functions
section or page 9 for detail description of each timing
function.

t Unit

Sets the display units of measure. See below table for a
list of the available units.

T oUt 1

Sets the pulse width (t) for output 1. The default output timeis
0.02 seconds. If you wish the system to keep the operation of
the output, please set the output time to 0.00 seconds.

rtSr

Sets the minimum pulse width at either 1 msec or 20 msec.

inPtLC

Sets the transistor input type to NPN or PNP. For contact input,
the selection can be either PNP or NPN, but the selection will
determine whether the connection is to terminal 11 or terminal 6.
See the input connection diagrams on page 5.

Page 8

Display
S 001
S 01
S 1
mS 001
mS 01
m 01
M 1
HmS
Hm 1
H 1

Units
sec.
sec.
sec.
min., sec.
min., sec.
Min.
Min.
Hr., min., sec.
Hr., min.
Hr.

Range
0.01 to 9,999.99
0.1 to 99,999.9
1 to 999,999
0.01 to 9,959.99
0.1 to 99,959.99
0.1 to 99,999.9
1 to 999,999
1 to 995,959
1 to 999,959
1 to 999,999

Resolution
10 msec.
0.1 sec.
1 sec.
10 msec.
0.1 sec.
0.1 min.
1 min.
1 sec.
1 min.
1 hr.

Maximum Time
9,999.99 sec.
99,999.9 sec
999,999 sec.
5,999.99 sec.
59,999.9 sec.
99,999.9 min.
999,999 min
359,999 sec. (100 hr.)
599,999 min. (10,000 hr.)
699,999 hr.

Table A: List of Timing Units