beautypg.com

Dwyer LCT216 User Manual

Page 16

background image

Page 16

PuErS

Power Save feature allows the control to save the current process
value upon loss of power.

SAvE

Save process value upon power loss

CLEAr

Clear process value upon power loss

rtSr

Minimum width of reset signal determines how long the reset
terminals must be engaged to reset the device.

inPtLC

Input signal can be set for PNP or NPN. This parameter
determines which wiring diagram should be used.

DIP SWITCH SETTINGS

The Series LCT216 can be configured either using the configuration parameters discussed
in the previous section or by using DIP switches located on the side of the housing. When
the DIP switch setting is turned on, the parameters can be viewed, but not changed using
the front panel.

SW
8

7

6

5

4

3

2

1

Counter
Reset Pulse Width
On = 1 ms, Off = 20 ms
Input Type
On = PNP, Off = NPN
N/A

Counting Speed
On = 10K CPS, Off = 30 CPS
Output Mode of Counter
See Table D
Output Mode of Counter
See Table D
Input Mode of Counter
On = Down, Off = Up
On = Enable DIP Switch
Off = Disable DIP Switch

Timer
Reset Pulse Width
On = 1 ms, Off = 20 ms
Units of Timer
See Table C
Units of Timer
See Table C
Units of Timer
See Table C
Output Mode of Timer
See Table D
Output Mode of Timer
See Table D
Time Counting Up/Down
On = Down, Off = Up
On = Enable DIP Switch
Off = Disable DIP Switch

Tachometer
Reset Pulse Width
On = 1 ms, Off = 20 ms
Input Type
On = PNP, Off = NPN
N / A

Counting Speed
On = 10KHz, Off = 30 Hz
Output Mode of Tachometer
See Table D
Output Mode of Tachometer
See Table D
N / A

On = Enable DIP Switch
Off = Disable DIP Switch

Table B: DIP Switch Parameter List