TACHOMETER SETTINGS

Parameter Configuration
PV

SV

FUnC

tACH

Sets the controller to function as a tachometer.

tAotmd

Tachometer Output Mode determines the output condition when the
process value exceeds the set point value. See output mode charts
below for more information.

C SPEd

Maximum Input Frequency can be set from one count per second up
to 10,000 counts per second.

Point

Sets the number of digits to the right of the decimal point on the
display.

PSCALE

Pre-Scale is used when converting the process value’s units of
measure. This value is commonly used to convert the input
frequency (counts per second) to a rotational speed (rpm) using the
below equation.

Frequency (Hz) * Pre-Scale = Rotation Speed (rpm)

Pre-Scale = 60 / n (where n = number of pulses per

revolution).

St tAC

Initial Power Up Interrupt delays the output from triggering for up to
99.9 seconds.

St AvG

Input Filter allows the tachometer to average 2, 4, or 8 readings to
give a more stable reading. (1= 2 data points, 2 = 4 data points, and
3 = 8 data points).

rtSr

Minimum Width of Reset Signal determines how long the
reset terminals must be engaged to reset the device.

inPtLC

Input signal can be set for PNP or NPN. This parameter
determines which wiring diagram should be used.

Tachometer Output Mode Charts

OUT2 set value

Measurement value

OUT1 set value

OUT1

OUT2

OUT1 set value : OUT1 ON

Measurement value

OUT2 set value : OUT2 ON

(LO-LO)

OUT2 set value

Measurement value

OUT1 set value

OUT1

OUT2

Measurement value

OUT1 set value : OUT1 ON

Measurement value

OUT2 set value : OUT2 ON

(LO-HI)

OUT2 set value

Measurement value

OUT1 set value

OUT1

OUT2

(HI-LO)

Measurement value OUT1 set value : OUT1 ON

Measurement value OUT2 set value : OUT2 ON

OUT2 set value

Measurement value

OUT1 set value

OUT1

OUT2

(HI-HI)

Measurement value OUT1 set value : OUT1 ON

Measurement value OUT2 set value : OUT2 ON