Input ranges – Dwyer 16A User Manual
Page 43
Page 43
Termination: 120 Ohms, balanced.
1
Number can be increased through use of a repeater such as the Mother
Node™. Consult factory for details.
INPUT RANGES
INPUT TYPE
RANGE °F
RANGE °C
Type J or L
1
Thermocouple
-100 to +1607
-73 to +871
Type K
1
Thermocouple
-200 to +2500
-129 to +1371
Type T
1
Thermocouple
-350 to +750
-212 to +398
Type E
1
Thermocouple
-100 to +1800
-73 to +982
Type R Thermocouple
0 to 3200
-17 to +1760
Type S Thermocouple
0 to 3200
-17 to +1760
Type B Thermocouple
+75 to +3308
+24 to +1820
Type C Thermocouple
0 to 4208
-17 to +2320
Type N
1
Thermocouple
-100 to +2372
-73 to +1300
100
Ω Plt. 0.00385 DIN
1
RTD
-328 to 1607
-200 to +875
100
Ω Plt. 0.00392 NIST
1
RTD
-328 to 1607
-200 to +875
120
Ω Nickel 0.00628 US
1
RTD
-112 to +608
-80 to +320
1000
Ω Plt. 0.00385 DIN
1
RTD
-328 to +1607
-200 to +875
Current/Voltage/
ΔVoltage
2
Scalable Units from -1999 to +9999
1
These Input Types can be set for 0.1°display. If temperature goes above
999.9°or less than -199.9°the display will return to whole degree resolution.
2
The 0 to 20 mADC, 4 to 20 mADC, 0 to 10 VDC, 2 to 10 VDC, and -10 to +10
mVDC inputs are fully scalable from a minimum of 100 counts span placed any
where within the within the range of -1999 to +9999. Decimal point position is
adjustable from the zero place (9999), tenths (999.9), hundredths (99.99), thou-
sandths (9.999), or ten thousandths (.9999).
949-1265:Layout 1 1/25/11 10:23 AM Page 43