(Option 948, 4-Stage Set Point) Active Set Point Stage. Select

1SP1

,

25P1

,

35P1

,

45P1

. (See Page 17 for more detail.)

1SP1

Set Menu Items to display Stage 1 for view and change access. If

SPSA

is set for

1nt

,

1SP1

is made active.

25P1

Set Menu Items to display Stage 2 for view and change access. If

SPSA

is set for Int,

25P1

is made active.

35P1

Set Menu Items to display Stage 3 for view and change access. If

SPSA

is set for Int,

35P1

is made active.

45P1

Set Menu Items to display Stage 4 for view and change access. If

SPSA

is set for

1nt

,

45P1

is made active.

#

SP1

(Option 948, 4-Stage Set Point) Adjust Control Point 1 for Stage selected
above.

Note: The menu items for

tunE

(below) are modified when Option 948 is active.

Then, the menu items are shortened or shifted right, and preceded with the stage
number selected in

SP

above. Each stage has its own set of

tunE

parameters as

indicated by #

tun

.

#

tun

(Option 948, 4-Stage Set Point) or

tunE

Tuning Choice: Select

SELF

,

Pid

,

SL0, nor

, or

FASt

.

SELF

The Controller will evaluate the Process and select the PID values
to maintain good control. Active for SP1 only.

LErn

Select

YES

or

no

YES

Start Learning the Process. After the process has
been learned the menu item will revert to

no

.

no

Learning will stay in present mode.

dFAC

Damping factor, select

0FF

,

1

to

7

. Sets the ratio of Rate

to Rate for the

SEL tunE

mode.

7

= most Rate. Factory set

to

3

. For a fast response process the value should be low-

ered (less Rate). For a slower process the value should be
increased (more Rate).

Pid

Manually adjust the PID values. PID control consists of three basic
parameters, Proportional Band (Gain), Reset Time (Integral), and
Rate Time (Derivative).

Pb1

Proportional Band (Bandwidth). Select

1

to

9999

°F, °C,

or counts.

Pb2

Proportional Band (Bandwidth). Select

1

to

9999

°F, °C,

or counts. Appears only if control is equipped with second
set point and

0ut2

is NOT selected as

0n0F

.

Page 23