to program the target set point and the time desired to reach that point. When the
ramp segment is executed by the control, it calculates the ramp required to move
the process from the starting value (current PV) to the desired value (programmed
SP) in the time allowed.

Soaks (or dwells) are ramp segments where the target set point is the same as the
beginning process value. This allows for multistage ramps without wasting interme-
diate soak steps. Care must be taken, however, that the process does actually reach
the soak value before the soak time starts. If not, the next segment will calculate a
slope from the starting PV to the target SP. Depending on your process require-
ments, this difference may be important. Make sure to test any program for desired
results before running production material.

Do not operate Self Tune while a ramp function is operating. The ramp func-
tion will prevent the Self Tune from operating properly. Make sure that all
tuning is set up before operating Ramp / Soak.

Program Setup

All of the programming for the Ramp / Soak function is done in the Secondary Menu.
You may wish to work out your program on paper before going into the programmer
menu sequence.

In the Secondary Menu INDEX to

Pro9

and make sure that

Pro9

is set to

0FF

.

INDEX to

PSEt

and turn

0n

. Press ENTER.

Skip the

StAt

setting (this is discussed later) and press INDEX to

tbAS

.

The time base menu item,

tbAS

, allows selection of the amount of time that is count-

ed per time unit. Setting

tbAS

to

1

makes all time settings use a time base of one

second. A

tbAS

setting of

60

makes all times settings use a time base of 60 sec-

onds, or one minute. Make the appropriate selection and then press ENTER

and INDEX to

1ti

.

The following items repeat in the following order:

1ti , 1SP, 1A1

(if

AL1

in the Secure

Menu is programmed set to

EUnt

),

2ti , 2SP, 2A1, . . . , 16ti, 16SP, 16A1

. To avoid

repetition each item will only be described once.

Set

1ti

to the amount of time you want for the first ramp. This value is in time units

(determined by the

tbAS

menu item) from

0

to

9999

. Press ENTER.