to program the target set point and the time desired to reach that point. When the
ramp segment is executed by the control, it calculates the ramp required to move
the process from the starting value (current PV) to the desired value (programmed
SP) in the time allowed.
Soaks (or dwells) are ramp segments where the target set point is the same as the
beginning process value. This allows for multistage ramps without wasting interme-
diate soak steps. Care must be taken, however, that the process does actually reach
the soak value before the soak time starts. If not, the next segment will calculate a
slope from the starting PV to the target SP. Depending on your process require-
ments, this difference may be important. Make sure to test any program for desired
results before running production material.
Do not operate Self Tune while a ramp function is operating. The ramp func-
tion will prevent the Self Tune from operating properly. Make sure that all
tuning is set up before operating Ramp / Soak.
Program Setup
All of the programming for the Ramp / Soak function is done in the Secondary Menu.
You may wish to work out your program on paper before going into the programmer
menu sequence.
In the Secondary Menu INDEX to
Pro9
and make sure that
Pro9
is set to
0FF
.
INDEX to
PSEt
and turn
0n
. Press ENTER.
Skip the
StAt
setting (this is discussed later) and press INDEX to
tbAS
.
The time base menu item,
tbAS
, allows selection of the amount of time that is count-
ed per time unit. Setting
tbAS
to
1
makes all time settings use a time base of one
second. A
tbAS
setting of
60
makes all times settings use a time base of 60 sec-
onds, or one minute. Make the appropriate selection and then press ENTER
and INDEX to
1ti
.
The following items repeat in the following order:
1ti , 1SP, 1A1
(if
AL1
in the Secure
Menu is programmed set to
EUnt
),
2ti , 2SP, 2A1, . . . , 16ti, 16SP, 16A1
. To avoid
repetition each item will only be described once.
Set
1ti
to the amount of time you want for the first ramp. This value is in time units
(determined by the
tbAS
menu item) from
0
to
9999
. Press ENTER.
Set
like
temp
set i
Pres
then
set
Alarm
Com
16SP
For u
set t
poin
you
The
cont
repe
puts
It is
the p
ed. R
begi
feren
Ram
Whe
men
or by
DOW
The
HOL
three
To s
agai
Page 12
949-1265:Layout 1 1/25/11 10:22 AM Page 12