Operating of Self Tune Function

Self Tune allows automatic selection of the necessary parameters to achieve best
control operation from your 16A2 & 16A3 Series control. If you are using the con-
trol output as a simple on-off function (

0ut 1

set for

0n0F

), none of the following

will apply.

Theory of Operation

The Self Tune function calculates the

Pb1

,

rES

, and

rtE

parameters under the

Pid

tunE

selection, and the

Fbnd

and

FrtE

parameters, as shown in the Secondary

Menu. These values are determined by measuring the response of the process con-
nection to the control. While in this mode the control measures the overshoot and
undershoot of the process, and the period of the process (the time from peak value
to the next peak value). These measurements are collected over a period that lasts
three periods of overshoot and undershoot. The data collected over this time is effect
of Fuzzy Logic on the process is still controlled by the

Fint

(fuzzy intensity) setting.

If

Fint

is

0

, the

Fbnd

and

FrtE

will be calculated, but will have no effect. The calcu-

lations for the PID values are the same as used in the standard Ziegler - Nichols
equations that have been recognized as standard for decades.

The only modification to the application of the Ziegler - Nichols equations is con-
trolled by the

dFAC

menu item. This menu item controls the amount of rate (deriva-

tive) that is applied. A

dFAC

setting of 3 (factory default) or less allows for less damp-

ing. A

dFAC

setting of 4 allows for critical damping as set forth in Ziegler - Nichols. A

dFAC

setting of 5 or more allows over damping of the process.

Program Setup and Operation

Do not cool the process or add heat while the tuning is occurring. In the secondary
menu set

tunE

to

SELF

. Skip

LErn

and check to make sure that

dFAC

is set to the

desired value. Back up to

LErn

and set to

YES

. The control will begin the Self Tune

function. While the Self Tune function is active, the right hand decimal point on the
lower display will blink. When Self Tune is complete, the blinking will stop.

After Self Tune is complete, the

tunE

setting automatic switches to

Pid

. This allows

examination and/or modification of the values calculated. We recommended that you
do not change the calculated values unless you have a firm understanding of the
parameters involved and their function.