Dwyer 16A User Manual
Page 35
Page 35
The following menu items apply only to the alarm.
AL1
Alarm 1 function: Select
0FF, Lo, Hi, HiLo,
or
EUnt
.
0FF
Alarm 1 is disabled. No Alarm 1 menu items appear in the
Secondary or Secure menus.
Lo
Low Alarm Only.
A1Lo
appears in the Secondary
Menu.
Hi
High Alarm Only.
A1Hi
appears in the Secondary Menu.
HiLo
High and Low Alarms. Both
A1Lo
and
A1Hi
appear in the
Secondary Menu, and share the same Alarm 1 Relay output.
EUnt
Alarm 1 is controlled by the Ramp/Soak program function.
(16A3). See Pages 11-14 and 26 (#A1) for further information.
If
AL1
is set to
0FF
and the control is not equipped with options, the Secure Menu
ends here. If
AL1
is set to
0FF
and the control is equipped with options, proceed to
SPSA
,
Addr
, or
rSCL
below.
If
AL1 is set to EUnt, go to A1St below.
A1t
Alarm 1 Type: Select
AbS
or
dE
AbS
Absolute Alarm that may be set anywhere within the values of
SCAL
and
SCAH
and is independent of
SP1
.
dE
Deviation Alarm that may be set as an offset from
SP1
. As
SP1
is
changed the Alarm Point will track with
SP1
.
A1rE
Alarm 1 Reset: Select
0n0F
or
HoLd
.
0n0F
Automatic Reset.
HoLd
Manual Reset. Reset (acknowledge) by simultaneously pressing the
INDEX & DOWN ARROW keys for 3 seconds.
A1Pi
Alarm 1 Power Interrupt: Select
0n
or
0FF
.
0n
Alarm Power Interrupt is
0n
.
0FF
Alarm Power Interrupt is
0FF
.
A1iH
Alarm 1 Inhibit: Select
0n
or
0FF
.
0n
Alarm Inhibit is
0n
. Alarm action is suspended until the process
value first enters a non-alarm condition.
0FF
Alarm Inhibit is
0FF
.
A1St
Alarm 1 Output State: Select
CL0S
or
0PEn
.
CL0S
Closes Contacts at Alarm Set Point.
0PEn
Opens Contacts at Alarm Set Point.