The following menu items apply only to the alarm.

AL1

Alarm 1 function: Select

0FF, Lo, Hi, HiLo,

or

EUnt

.

0FF

Alarm 1 is disabled. No Alarm 1 menu items appear in the
Secondary or Secure menus.

Lo

Low Alarm Only.

A1Lo

appears in the Secondary

Menu.

Hi

High Alarm Only.

A1Hi

appears in the Secondary Menu.

HiLo

High and Low Alarms. Both

A1Lo

and

A1Hi

appear in the

Secondary Menu, and share the same Alarm 1 Relay output.

EUnt

Alarm 1 is controlled by the Ramp/Soak program function.
(16A3). See Pages 11-14 and 26 (#A1) for further information.

If

AL1

is set to

0FF

and the control is not equipped with options, the Secure Menu

ends here. If

AL1

is set to

0FF

and the control is equipped with options, proceed to

SPSA

,

Addr

, or

rSCL

below.

If

AL1 is set to EUnt, go to A1St below.

A1t

Alarm 1 Type: Select

AbS

or

dE

AbS

Absolute Alarm that may be set anywhere within the values of

SCAL

and

SCAH

and is independent of

SP1

.

dE

Deviation Alarm that may be set as an offset from

SP1

. As

SP1

is

changed the Alarm Point will track with

SP1

.

A1rE

Alarm 1 Reset: Select

0n0F

or

HoLd

.

0n0F

Automatic Reset.

HoLd

Manual Reset. Reset (acknowledge) by simultaneously pressing the

INDEX & DOWN ARROW keys for 3 seconds.

A1Pi

Alarm 1 Power Interrupt: Select

0n

or

0FF

.

0n

Alarm Power Interrupt is

0n

.

0FF

Alarm Power Interrupt is

0FF

.

A1iH

Alarm 1 Inhibit: Select

0n

or

0FF

.

0n

Alarm Inhibit is

0n

. Alarm action is suspended until the process

value first enters a non-alarm condition.

0FF

Alarm Inhibit is

0FF

.

A1St

Alarm 1 Output State: Select

CL0S

or

0PEn

.

CL0S

Closes Contacts at Alarm Set Point.

0PEn

Opens Contacts at Alarm Set Point.