Optichill freecool active cabinet exhaust chillers, Chillers, Electrical data extra quiet continued – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 84

OptiChill Freecool
Active Cabinet Exhaust
Chillers
84
Chillers
Technical Manual : 7197700 v1.2.0. 02_2013
Electrical Data Extra Quiet Continued
30
31
32
Notes
Units
OFC102X18-99HL6
OFC076X20-66HS1
OFC081X20-76ML2
Unit Data
Nominal Run Amps (1)
A
577
428
435
Maximum Start Amps
A
1116
825
695
Recommended Mains Fuse Size
A
710
560
560
Mains Supply
VAC
400 V 3 PH 50 Hz
400 V 3 PH 50 Hz
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Direct to Bus Bar
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
4 mm² terminals
4 mm² terminals
Control Circuit
VAC
24V/230VAC
24V/230VAC
24V/230VAC
Evaporator
Trace Heater Rating
W
250
250
250
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
18
20
20
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
18
20
20
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Condenser Fan - Per Fan (HAEC)
Quantity
18
20
20
Full Load Amps
A
4.5
4.5
4.5
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.86
2.86
2.86
Compressor - Per Compressor
Quantity
1 + 1
1 + 1
1 + 1
Nominal Run Amps
A
266.2 / 266.2
188.9 / 188.9
205.5 / 179.9
Motor Rating
kW
152.7 / 152.7
105.0 / 105.0
122.5 / 105.0
Sump Heater Rating
W
300
300
300
Start Amps (2)
A
805 / 805
586 / 586
465 / 436
Type Of Start
Star - Delta
Star - Delta
Star - Delta
OPTIONAL EXTRAS
Low Ambient Kit
Recommended Permanent Fuse Size
A
32
32
32
Permanent Supply
VAC
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
4 mm² terminals
4 mm² terminals
Power Factor Correction
Unit Nominal Run Amps (1)
A
509
369
396
Maximum Start Amps
A
1082
796
675
Compressor Nominal Run Amps
A
232.0 / 232.0
159.5 / 159.5
186.1 / 159.5
Recommended Mains Fuse Size
A
710
560
560
Standard Head Pump (Single or Run/Standby)
Unit Nominal Run Amps
A
599
449
450
Recommended Mains Fuse Size
A
750
560
560
Pump Full Load Amps
A
21.2
21.2
14.8
Motor Rating
kW
11
11
7.5
Larger Head Pump (Single or Run/Standby)
Unit Nominal Run Amps
A
599
456
464
Recommended Mains Fuse Size
A
800
560
560
Pump Full Load Amps
A
21.2
28.5
28.5
Motor Rating
kW
11
15
15
Standard Head Inverter Pump (Single or Run/Standby)
Unit Nominal Run Amps
A
599
449
450
Recommended Mains Fuse Size
A
750
560
560
Pump Full Load Amps
A
21.2
21.2
14.8
Motor Rating
kW
11
11
7.5
Larger Head Inverter Pump (Single or Run/Standby)
Unit Nominal Run Amps
A
599
456
464
Recommended Mains Fuse Size
A
800
560
560
Pump Full Load Amps
A
21.2
28.5
28.5
Motor Rating
kW
11
15
15
(1) Based at 5.0 Evaporating, 50 Condensing, AC Standard Fans.
(2) Starting amps refers to the Star (
Ү) connection only.