Grooved & clamped type connection, Chillers optichill freecool – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 115
![background image](/manuals/370941/115/background.png)
Chillers
OptiChill Freecool
Chillers
115
Technical Manual :
7197700 v1.2.0 02_2013
Grooved & Clamped
Type Connection
1
Place Grooved Ends Together
2
Locate Rubber Gasket
Note that an expansion gap of 5mm is
shown here
The gasket should be checked for
compatability and damage prior
to installation.
A thin coat of sealing lubricant should
be applied to both the inside and
outside mating surfaces.
Slip the gasket fully onto one of the
pipe ends, align the second pipe and
slide the gasket into place.
3
Place Clamp over Gasket
4
Secure Clamp
Wrap the 2-halves of the clamp over
the gasket.
Ensure the gasket fits snugly within the
grooved recess inside the clamp and
that the clamp seats correctly.
Tighten the bolts incrementally and
evenly at both sides until a leak free
seal is formed.
The gasket should not be visible
beneath the clamp when the bolts are
properly tightened.