Interconnecting wiring, Interconnecting, Wiring – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 118: Optichill freecool active cabinet exhaust chillers, Installation data, Chillers, Caution
OptiChill Freecool
Active Cabinet Exhaust
Chillers
118
Chillers
Technical Manual : 7197700 v1.2.0. 02_2013
Installation Data
Interconnecting Wiring
OFC
L1
Mains incoming supply 400V/3PH/50Hz
L2
L3
PE
L4
Separate Permanent Supply 230V / 1PH +N / 50Hz
N1
(1)
PE
L4
External Trace Heating Connections
N1
230V/500W max
502
(2)
Remote Pump Interlock 24VAC
507
502
(2)
Evaporator Pump Water Flow Switch 24VAC
505
502
Unit Remote On/Off 24VAC
504
502
Setback Setpoint Temperature switch
506
581
Non-
Critical
Alarm
Volt Free Common Alarm
580
Volt Free Alarm N/O
582
Volt Free Alarm N/C
591
Critical
Alarm
Volt Free Common Alarm
590
Volt Free Alarm N/O
592
Volt Free Alarm N/C
RX-/Tx-
RX+/Tx+
IN
GND
Network Connections
RX-/Tx-
RX+/Tx+
OUT
GND
CAUTION
(1) A separate permanent supply ensures that essential items such as crankcase
heaters / trace heating are energised at all times. Failure to do may cause unit
malfunction.
(2) MUST be directly wired to the chiller to validate warranty.