Water system, Standard recommended installation, Optichill freecool active cabinet exhaust chillers – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 114: Installation data
OptiChill Freecool
Active Cabinet Exhaust
Chillers
114
Chillers
Technical Manual : 7197700 v1.2.0. 02_2013
Installation Data
Water system
Chilled water pipework and ancillary components must be installed in accordance with:
National and Local Water supply company standards
The manufacturer's instructions are followed when fitting ancillary components
The system liquid is treated to prevent corrosion and algae forming
In ambients of 0°C and below, where static water can be expected, or when water
supply temperatures of +5°C or below is required, the necessary concentration of
Glycol or use of an electrical trace heater must be included
The schematic is referred to as a guide to ancillary recommendations
CAUTION
The unit water connections are NOT designed to support external pipework,
pipework MUST be supported separately.
Standard recommended installation
(Parts Supplied by Others)
General
The following diagram illustrates the minimum component installation requirements. A
wide range of optional extras are available to suit various applications.
CAUTION
The following installation recommendations should be adhered to. Failure to do
this may invalidate the chiller warranty.
P
T
(10)
(9)
(4)
(7)
(3)
(2)
(1)
(6)
(8)
(11)
(12)
T
P
(5)
(1) Flexible connections
(2) Pressure gauges
(3) Temperature gauges
(4) Binder points
(5) De-aerator (optional extra)
(6) Auto air vent (at highest point)
(7) Strainer (optional extra)
(8) Flow switch
(9) Shut off valves
(10) Bypass circuit (for flushing)
(11) Pump
(12) Pump strainer
CAUTION
Full design water flow MUST be maintained at all times. Variable water volume is
NOT recommended and will invalidate warranty
CAUTION
The correct operation of the flow proving device is critical if the chiller warranty is
to be valid.
CAUTION
Following components are fitted within the chiller unit as standard:
Temperature Sensors
Drain Point
Auto Air Vent