Positioning
The installation position should be selected with the following points in mind:
Position on a stable and even base, levelled to ensure that the compressor
operates correctly
Levelling should be to +/- 5mm
Where vibration transmission to the building structure is possible, fit spring anti-
vibration mounts and flexible water connections
Observe airflow and maintenance clearances
Pipework and electrical connections are readily accessible
Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity
Within a side enclosed installation, the fan MUST be higher than the
enclosing structure
Increase airflow and maintenance clearances for side-enclosed or multiple
unit applications
Ensure there are no obstructions directly above the fans
Allow free space above the fans to prevent air recirculation
CAUTION
Prior to connecting services, ensure that the equipment is installed and
completely level.
Airflow & Maintenance
Clearances
1300mm / (2600mm)
(1)
(1)
(1)
Application
Distance from Overall Base Dimension
Single unit
1300mm
Side-enclosed or multiple units
2600mm