Optichill freecool active cabinet exhaust chillers, Chillers, Electrical data regular quiet continued – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 78
OptiChill Freecool
Active Cabinet Exhaust
Chillers
78
Chillers
Technical Manual : 7197700 v1.2.0. 02_2013
Electrical Data Regular Quiet Continued
13
14
15
Notes
Units
OFC092R20-87MS4
OFC099R20-88HS6
OFC108R20-99HL6
Unit Data
Nominal Run Amps (1)
A
533
577
618
Maximum Start Amps
A
878
1136
1157
Recommended Mains Fuse Size
A
670
710
750
Mains Supply
VAC
400 V 3 PH 50 Hz
400 V 3 PH 50 Hz
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Direct to Bus Bar
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
4 mm² terminals
4 mm² terminals
Control Circuit
VAC
24V/230VAC
24V/230VAC
24V/230VAC
Evaporator
Trace Heater Rating
W
250
250
250
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
20
20
20
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
20
20
20
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Condenser Fan - Per Fan (HAEC)
Quantity
20
20
20
Full Load Amps
A
4.5
4.5
4.5
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.86
2.86
2.86
Compressor - Per Compressor
Quantity
1 + 1
1 + 1
1 + 1
Nominal Run Amps
A
241.3 / 205.5
245.4 / 245.4
266.2 / 266.2
Motor Rating
kW
139.5 / 122.5
138.8 / 138.8
152.7 / 152.7
Sump Heater Rating
W
300
300
300
Start Amps (2)
A
586 / 465
805 / 805
805 / 805
Type Of Start
Star - Delta
Star - Delta
Star - Delta
OPTIONAL EXTRAS
Low Ambient Kit
Recommended Permanent Fuse Size
A
32
32
32
Permanent Supply
VAC
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
4 mm² terminals
4 mm² terminals
Power Factor Correction
Unit Nominal Run Amps (1)
A
484
508
550
Maximum Start Amps
A
858
1102
1123
Compressor Nominal Run Amps
A
211.9 / 186.1
210.9 / 210.9
232.0 / 232.0
Recommended Mains Fuse Size
A
670
710
750
Standard Head Pump (Single or Run/Standby)
Unit Nominal Run Amps
A
568
605
640
Recommended Mains Fuse Size
A
710
750
800
Pump Full Load Amps
A
35
28.5
21.2
Motor Rating
kW
18.5
15
11
Larger Head Pump (Single or Run/Standby)
Unit Nominal Run Amps
A
574
612
647
Recommended Mains Fuse Size
A
710
750
800
Pump Full Load Amps
A
41.5
35
28.5
Motor Rating
kW
22
18.5
15
Standard Head Inverter Pump (Single or Run/Standby)
Unit Nominal Run Amps
A
568
605
640
Recommended Mains Fuse Size
A
710
750
800
Pump Full Load Amps
A
35
28.5
21.2
Motor Rating
kW
18.5
15
11
Larger Head Inverter Pump (Single or Run/Standby)
Unit Nominal Run Amps
A
574
612
647
Recommended Mains Fuse Size
A
710
750
800
Pump Full Load Amps
A
41.5
35
28.5
Motor Rating
kW
22
18.5
15
(1) Based at 5.0 Evaporating, 50 Condensing, AC Standard Fans.
(2) Starting amps refers to the Star (
Ү) connection only.