Glycol data, Chillers optichill freecool, Performance data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 53
Chillers
OptiChill Freecool
Chillers
53
Technical Manual :
7197700 v1.2.0 02_2013
Performance Data
Glycol Data
For a given percentage of glycol in the system there are correction factors that need to
be applied, the following tables can be used as a guide.
CAUTION
The source data must be at 20% Glycol for the correction factors to be valid.
This data is for a guide only. Please contact Airedale for accurate figures.
Where:
Output
= (kW) Output (kW)
Compressor Input
= (kW) Input (kW), (-) Minus TFP
TFP
(Total Fan Power)
= (kW) Quantity of Fans to unit x Fan Motor Size.
Water Flow
= (l/s) ALWAYS USE 20% Glycol Specific heat Capacity of 3.9.
ΔT
= (°C) Difference of Entering Water and Leaving Water temperature
Ethylene Glycol Nominal Correction Factors
Glycol in System / Freezing
Point ºC
20% / -9°C
30% / -15°C
40% / -23°C
Cooling Duty
x by
1.00
0.98
0.96
Input Power
1.00
0.98
0.97
Water Flow
1.00
1.02
1.05
Pressure Drop
1.00
1.15
1.31
Propylene Glycol Nominal Correction Factors
Glycol in System / Freezing
Point ºC
20% / -6°C
30% / -12°C
40% / -20°C
Cooling Duty
x by
1.00
0.96
0.93
Input Power
1.00
0.98
0.97
Water Flow
1.00
0.98
0.98
Pressure Drop
1.00
1.13
1.25
Example OFC076R16-66HS1 operating at 10/15, 35°C Ambient, 30% Ethylene Glycol
Cooling kW
(752.2)
x 0.98
30% Ethylene
Glycol =
737.2 kW
Input kW
(264.7)
x 0.98
259.4 kW
Flow l/s
(38.6)
(calculated:
3.9
x
T
(Output)
)
x 1.02
39.37 l/s
Pressure Drop kPa (107.8)
x 1.15
124 kPa