Chillers optichill freecool, Chillers, Mechanical data – regular quiet continued – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 57
![background image](/manuals/370941/57/background.png)
Chillers
OptiChill Freecool
Chillers
57
Technical Manual :
7197700 v1.2.0 02_2013
Mechanical Data
– Regular Quiet Continued
7
8
Notes
Units
OFC083R18-76ML2
OFC091R18-87HS4
2 Row Free Cool
3 Row Free Cool
2 Row Free Cool
3 Row Free Cool
Cooling Duty - AC Fans
1
kW
822.7
817.8
906
900.3
Nom Input -Cooling Only
kW
283.8
286.5
324.9
328.2
EER
2
2.9
2.85
2.79
2.74
ESEER
7
2.93
2.88
2.92
2.88
SEER
7
2.91
2.86
2.89
2.85
Nominal Output - Free Cooling
5
kW
640.1
716.3
658.8
741
Ambient when Free Cooling = 100% Nominal DX
6
°C
-0.4
1.3
-1.5
0.4
Cooling Duty - EC Fans
1
kW
820.9
817.6
909.4
906.1
Nom Input -Cooling Only
kW
277
280.3
320.3
324.2
EER
2
2.96
2.92
2.84
2.8
ESEER
7
3.28
3.23
3.24
3.19
SEER
7
3.23
3.18
3.18
3.13
Nominal Output - Free Cooling
5
kW
663.4
746.3
685.4
776
Ambient when Free Cooling = 100% Nominal DX
6
°C
0.2
1.9
-0.9
1
Cooling Duty - High Airflow EC Fans
1
kW
820.6
817.2
908.8
905.4
Nom Input -Cooling Only
kW
277.1
280.4
320.3
324.3
EER
2
2.96
2.91
2.84
2.79
ESEER
7
3.26
3.21
3.23
3.18
SEER
7
3.21
3.16
3.17
3.12
Nominal Output - Free Cooling
5
kW
683.5
771.1
707.3
803.5
Ambient when Free Cooling = 100% Nominal DX
6
°C
0.6
2.3
-0.4
1.5
Capacity Steps
%
20, 30, 40, 55, 65, 80, 90, 100
Dimensions (H x W x L)
mm
2600 x 2200 x 10850
2600 x 2200 x 10850
Machine Weight
kg
11620
11675
11770
11850
Operating Weight
3
kg
13980
14185
14175
14380
Construction Material
Base: Plain Galvanised Steel, Panels: Galvanised Sheet Steel, Epoxy Baked
Powder Paint, Light Grey (RAL 7035)
Evaporator - Type
Shell and Tube
Insulation
Class O / UV Stable
Total Max. Water Flow
l/s
58.1
58.1
79.2
79.2
Total Min. Water Flow
l/s
14.4
14.4
19.7
19.7
Condenser - Type
Rifled Copper Tube / Aluminium Fin
Face Area Total
m²
35.6
35.6
35.6
35.6
Maximum Airflow - High Airflow EC Fans
m³/s
95.5
91.3
95.5
91.3
Maximum Airflow - EC Fans
m³/s
89.1
85.1
89.1
85.1
Maximum Airflow - AC Fans
m³/s
81.6
77.5
81.6
77.5
Condenser Fan & Motor
Sickle Bladed Axial Fan
Quantity
18
18
18
18
Diameter
mm
800
800
800
800
Maximum Speed - High Airflow EC Fans
RPM
1080
1080
1080
1080
Maximum Speed - EC Fans
RPM
980
980
980
980
Maximum Speed - AC Fans
RPM
900
900
900
900
Compressor - Type
Semi-Hermetic Twin Screw Compressor
Quantity
2
2
2
2
Oil Charge Volume (Total)
l
35 + 35
35 + 35
35 + 35
35 + 35
Oil Type
BSE 170 Polyol Ester Oil
Refrigerant - Control
Electronic Expansion Valve
Refrigerant Pre-charged
R134a
Charge (Total) CCT1 + CCT2
kg
169 + 170
169 + 170
180 + 173
180 + 173
Water Connections
Type
Grooved Terminations
Inlet / Outlet - Unit
DN200
DN200
DN200
DN200
Water Drain / Bleed - Evap
inch
0.5
0.5
0.5
0.5
Water System - Volume
l
1520
1653
1554
1687
Minimum System Water Volume
4
l
3851
3976
4571
4695
Max System Operating Pressure
Bar
10
10
10
10
Flow Rate 20% Ethylene Glycol
l/s
44.3
44
48.8
48.5
Pressure Drop 20% Ethylene Glycol
kPa
150.1
130.4
129.2
106.4
(1) Based on units performance at 15/10°C return/supply temperatures, 35°C ambient, 20% Ethylene Glycol.
(2) EER = DX Cooling Output / (Compressor Input Power + Fan Input Power)
(3) Based on standard unit without options, operating weight includes refrigerant charge and water volume.
For unit weights with waterside options fitted please refer to Airedale.
(4) For minimum system water volume calculation, refer to Design Features & Information - Minimum System Water Volume Calculations.
(5) Nominal Free Cooling Output at 15/10°C return/supply temperatures, 3°C ambient, 20% Ethylene Glycol.
(6) Ambient temperature that Maximum Nominal DX Duty can be achieved using Free Cooling only.
(7) ESEER / SEER based upon unit operating at 12 / 7 °C return / supply temperature, 35°C ambient,