Minimum system water volume
METHOD 1
(Preferred Method)
Where the system permanent heat load is known, the minimum water volume in litres V
min
is:
V
min
=
Water Flow Rate (litres/min)
x
Minimum Compressor Run Time (min)
x
Chiller Loading Factor
Chiller Loading Factor
=
Minimum Turndown (kW) x 1.2
Permanent Heat Load
Minimum Turndown
=
17.5%
Example:
922.4kW Chiller at 35°C Ambient, 7/12°C Water, Model OFC095R20-87MS6 with a
permanent load of 553kW
Permanent Heat Load
= 553kW
Minimum Turndown
= 17.5%
V
min =
922.4 x 60
x 5 x
922.4 x 0.175
x 1.2 = 4631 Litres
4.186 x 5
553
METHOD 2
Where the system permanent heat load is unknown:
V
min
=
Water Flow Rate (litres/hour)
x
Minimum Turndown
x
1.2
x
Minimum Compressor Run Time (Hours)
+
Unit water volume
Minimum Turndown
=
17.5%
Example:
922.4kW Chiller at 35°C Ambient, 7/12°C Water, Model OFC095R20-87MS6
Minimum Turndown
= 0.175 (17.5%)
V
min =
922.4 x 3600
0.175 x 1.2 x
5
+ 1657= 4433 Litres
4.186 x 5
60