KS 800 CAN-Interface

3

Process data objects

Max. 4 bytes of usable data can be transmitted between two partners by means of SDOs. The
remaining 4 bytes are used for the command, the index and the subindex. With one PDO, howe-
ver, max. 8 bytes of usable data can be transmitted. Two send and two receive PDOs, which can
be defined as "synchronous PDOs" or as "asynchronous PDOs" via configuration, are supported
by KS800. For instance, the data transfer via the PDOs is purposeful, when controller process
values and status values must be sent to the master dependent of e.g. error messages (change-
of-state). In this case, asynchronous PDOs, which will be sent to the master automatically when
the event occurs on the controller are used. Another example would be cyclic enquiry of process
values by an operating unit. In this case, KS800 can send PDOs by synchronization with a clock
frequency (SYNC-EVENT).
As opposed to SDOs, PDOs are always non-acknowledged services. They can be received by
several units. As already mentioned above, this does not apply to SDOs.

In the KS800 default configuration, one asynchronous send and receive PDO with the following
identifiers are enabled:

COB-ID of the asynchronous receive PDO:

0x200 + node ID

COB-ID of the asynchronous send PDO:

0x180 + node ID

PDO reconfiguration is possible by means of SDO accesses to the following indexes:

default

default COB-ID

Index 1400:

first receive PDO

sync./disabled

300

Index 1401:

second receive PDO

async./enabled

200

Index 1800:

first send PDO

sync./disabled

280

Index 1801:

second send PDO

async./enabled

180

Configuration of the message identifier (COB-ID) as well as PD0 enabling and disabling are done
under subindex 1.

COB-ID (low byte)

data[ 1]

COB-ID (high byte)

data[ 2]

Enable

data[ 4]

(0x00 = enabled, 0x80 = disabled)

Transfer type configuration is under subindex 2.

Transfer type

data[ 1]

(0x01...0x0F = synch, 0xFF = async)

The PDO data contents are described in the following section.