4op mode / pre-op mode – West Control Solutions KS 800 CANopen Interface Manual User Manual
Page 15
KS 800 CAN-Interface
4
OP mode / pre-OP mode
After starting the CAN network, controller KS800 is in the pre-OP mode. I.e. it can be addressed
only via SDOs. When setting KS800 to the OP mode, communication via the enabled PDOs is
also possible. The asynchronous PDOs are enabled after start-up. If necessary, the synchronous
PDOs must be enabled via SDO messages.
Setting KS800 to OP mode:
2 data bytes
COB-ID
LEN
Command
Node
0x00
2
0x01
*
)
When selecting node address "0", all controllers in the network are set to the OP mode. The
controllers do not send a reply to this message.
Setting KS800 to pre-OP mode:
2 data bytes
COB-ID
LEN
Command
Node
0x00
2
0x80
*
)
When selecting node address "0", all controllers in the network are set to the pre-OP mode. The
controllers do not send a reply to this message.
Further NMT (Network-Management) - Commands:
Reset Node:
2 data bytes
COB-ID
LEN
Command
Node
0x00
2
0x81
*
)
Reset Communication:
2 data bytes
COB-ID
LEN
Command
Node
0x00
2
0x82
*
)
*
) NodeID-range within 1 ...127
Caution: Reset mode leads to a KS 800 reset, i.e. the controller will be accessible via
CAN-bus again only after several seconds. All Command-Parameters are set to the default
values.
9499 040 49511
15