KS 800 CAN-Interface

Example 2. A master reads a process value from a KS800 with node address 2:

The message structure is as follows:

COB_ID

= SDO at node 2

= 0x600 + 2

= 0x602

CMD

= read access

= 0x40

= 0x40

INDEX

= process value

= 0x2202

= 0x2202

SUBINDEX

= e.g. controller 3

= 03

= 0x03

8 data bytes

COB-ID

LEN

Cmd

Index

Sub.

Data

Enquiry:

(Master)

0x602

0x08

0x40

0x02
0x22

0x03

0x00

0x00

0x00

0x00

Reply:

(KS800)

0x582

0x08

0x4B

0x02
0x22

0x03

0xFA

0x00

0x00

0x00

WERT = 0x00FA = 250 = 25,0

°

C

By means of the SDOs, controller configuration and parameter setting can be adjusted via indi-
vidual accesses to all parameters (see object directory). However, addressing of all operating
data, which are normally transmitted via PDOs, can also be done via SDOs.