Technical data – West Control Solutions TB 40-1 Temperature Limiter User Manual
Page 27
Mounting
Panel mounting with two fixing clamps at
top/bottom or right/left. High-density mounting
possible
Mounting position:
uncritical
Weight:
0,27kg
Accessories delivered with the unit
Operating manual
Fixing clamps
Technical data
TB40-1
27
Range
Input resistance
Accuracy
Resolution (Ô)
0-10 Volt
~ 110 kW
Я 0,1 %
Я 0,6 mV
0-20 mA
49
W (voltage requirement ß 2,5 V)
Я 0,1 %
Я 1,5 mA
Table 3 Current and voltage measuring ranges
Type
Sens. current
Range
Accuracy
Resolution (Ô)
Pt100
0,2mA
-200...100°C
-140...212°F
ß 1K
0,1K
Pt100
-200...850°C
-140...1562°F
ß 1K
0,1K
Pt1000
-200...850°C
-140...392°F
ß 2K
0,1K
KTY 11-6 *
-50...150°C
-58...302°F
ß 2K
0,05K
* Or special
Table 2 Resistance transducer measuring ranges
Type
Range
Accuracy
Resolution (Ô)
L
Fe-CuNi (DIN)
-100...900°C
-148...1652°F
ß 2K
0,1 K
J
Fe-CuNi
-100...1200°C
-148...2192°F
ß 2K
0,1 K
K
NiCr-Ni
-100...1350°C
-148...2462°F
ß 2K
0,2 K
N
Nicrosil/Nisil
-100...1300°C
-148...2372°F
ß 2K
0,2 K
S
PtRh-Pt 10%
0...1760°C
32...3200°F
ß 2K
0,2 K
R
PtRh-Pt 13%
0...1760°C
32...3200°F
ß 2K
0,2 K
T
Cu-CuNi
-200...400°C
-328...752°F
ß 2K
0,05 K
C
W5%Re-W26%Re
0...2315°C
32...4199°F
ß 2K
0,4 K
D
W3%Re-W25%Re
0...2315°C
32...4199°F
ß 2K
0,4 K
E
NiCr-CuNi
-100...1000°C
-148...1832°F
ß 2K
0,1 K
B *
PtRh-Pt6%
0(100)...1820°C
32(212)...3308°F
ß 2K
0,3 K
* Specifications valid from 400°C
Table 1 Thermocouple measuring ranges