Contact type:
2 NO contacts with common
connection
Max. contact rating:
500 VA, 250 V, 2A at 48...62 Hz,
resistive load
Min. contact rating:
6V, 1 mA DC
Operating life (electr.): 800.000 duty cycles with max. rating
Note:
If the relays OUT1...OUT LC operate external
contactors, these must be fitted with RC
snubber circuits to manufacturer specifications
to prevent excessive switch-off voltage peaks.
POWER SUPPLY
Dependent of order
AC SUPPLY
Voltage:
90...250 V AC
Frequency:
48...62 Hz
Power consumption
approx. 7.3 VA
UNIVERSAL SUPPLY 24 V UC
AC voltage:
20,4...26,4 V AC
Frequency:
48...62 Hz
DC voltage:
18...31 V DC
Power consumption:
approx.. 7.3 VA
BEHAVIOUR WITH POWER FAILURE
Configuration, parameters and adjusted
set-points, control mode:
Non-volatile storage in EEPROM
BLUEPORT FRONT INTERFACE
Connection of PC via PC adapter (see
"Accessory equipment"). The BlueControl
software is used to configure, set parameters
and operate the TB40-1.
ENVIRONMENTAL CONDITIONS
Protection modes
Front panel:
IP 65 (NEMA 4X)
Housing:
IP 20
Terminals:
IP 00
Permissible temperatures
For specified accuracy:
0...60°C
Warm-up time:
≥ 15 minutes
For operation:
-20...65°C
For storage:
-40...70°C
Humidity
75% yearly average, no condensation
Altitude
To 2000 m above sea level
Shock and vibration
Vibration test Fc (DIN 68-2-6)
Frequency:
10...150 Hz
Unit in operation:
1g or 0,075 mm
Unit not in operation:
2g or 0,15 mm
Shock test Ea (DIN IEC 68-2-27)
Shock:
15g
Duration:
11ms
Electromagnetic compatibility
Complies with EN 61 326-1
(for continuous, non-attended operation)
GENERAL
Housing
Material:
Makrolon 9415 flame-retardant
Flammability class:
UL 94 VO, self-extinguishing
Plug-in module, inserted from the front
Safety test
Complies with EN 61010-1 (VDE 0411-1):
Overvoltage category II
Contamination class 2
Working voltage range 300 V
Protection class II
Certifications
Type tested to EN 14597 (2009-1)
With certified sensors applicable for:
w
Heat generating plants with outflow
temperatures up to 120°C to DIN 4751
w
Hot-water plants with outflow temperatures
above 110°C to DIN 4752
w
Thermal transfer plants with organic transfer
media to DIN 4754
w
O
il-heated plants to DIN 4755
Electrical connections
According to order:
w
- flat-pin terminals 1 x 6,3mm or 2 x 2,8mm
according to DIN 46 244 or
- screw terminals from 0,5 to 2,5mm².
Technical data