4.2 Configuration
Lim
Name
Value range Description
Default
Fcn.1
Function of limit 1
7
5
Measured value monitoring upper limit (no latching)
TW
1
6
Measured value monitoring lower limit (no latching)
TW
1
7
Measured value monitoring + latching of the alarm status of
the upper limit. A latched alarm can be reset by the error
list, the digital input or the RESET-key (->
LOGI/
Err.r).
TB
1
8
Measured value monitoring + latching of the alarm status of
the lower limit. A latched alarm can be reset by the error
list, the digital input or the RESET-key (->
LOGI/
Err.r).
TB
1
Fcn.2 / 3
Function of limit 2 / 3
0 / 0
0
switched off
1
measured value monitoring
2
Measured value monitoring + latching of the alarm status.
A latched alarm can be reset by the error list, the digital
input DI1 or the RESET-key (->
LOGI/ Err.r).
Src.2 / 3
Source of limit 2 / 3
0 / 0
0
process value
1
control deviation xw (process value - set-point)
Hour
OFF...10000
Operating hours (only visible with BlueControl!)
OFF
Swit
OFF...10000
Output switching cycles (only visible with BlueControl!)
OFF
1
TW: Temperature monitor
TB: Temperature limiter
+
Fcn.3, Src.3 only available if Fcn.1 is configured as TW
InP.1
Name
Value range Description
Default
S.tYP
Sensor type selection
1
0
thermocouple type L (-100...900°C), Fe-CuNi (DIN)
1
thermocouple type J (-100...1200°C), Fe-CuNi
2
thermocouple type K (-100...1350°C), NiCr-Ni
3
thermocouple type N (-100...1300°C), Nicrosil-Nisil
4
thermocouple type S (0...1760°C), PtRh-Pt10%
5
thermocouple type R (0...1760°C), PtRh-Pt13%
6
thermocouple type T (-200...400°C), Cu-CuNi
7
thermocouple type C (0...2315°C), W5%Re-W26%Re
8
thermocouple type D (0...2315°C), W3%Re-W25%Re
9
thermocouple type E (-100...1000°C), NiCr-CuNi
10
thermocouple type B (0/100...1820°C), PtRh-Pt6%
18
special thermocouple
Configuration level
TB40-1
15
Configuration