Engineering tool 17, Othr, Configuration level – West Control Solutions TB 40-1 Temperature Limiter User Manual
Page 17

othr
Name
Value range Description
Default
Unit
Unit
1
0
without unit
1
°C
2
°F
dP
Decimal point (max. number of digits behind the decimal
point)
0
0
No digit behind the decimal point
1
1 digit behind the decimal point
2
2 digits behind the decimal point
3
3 digits behind the decimal point
diSP
Type of measured value display
1
0
No measured value display
1
Full display resolution
2
Display resolution: 2 digits
3
Display resolution: 5 digits
4
Display resolution: 10 digits
C.dEl
0..200
Modem delay [ms]
0
FrEq
Switching 50 Hz / 60 Hz (only visible with BlueControl!)
0
0
50 Hz
1
60 Hz
g
Resetting the device configuration to factory setting (Default)
r chapter 10.1 (page 30)
+
BlueControl - the engineering tool for the BluePort
â
controller series
3 engineering tools with different functionality facilitating TB40-1 configuration
and parameter setting are available (see chapter 8: Accessory equipment with or-
dering information).
In addition to configuration and parameter setting, the engineering tools are used
for data acquisition and offer long-term storage and print functions. The enginee-
ring tools are connected to TB40-1 via the front-panel interface "BluePort
â
" by
means of PC and a PC adaptor.
Description BlueControl: see chapter 7: BlueControl (page 23).
Configuration level
TB40-1
17