West Control Solutions MRC 7000 Recorder Manual User Manual
Page 30
30
Unit Parameters
21 Relay A Assignment rLyA 0=Not assigned
0
1=Assigned to Alarm 1-Pen 1
2=Assigned to Alarm 2-Pen 1
3=Assigned to Alarm 1-Pen 2
4=Assigned to Alarm 2-Pen 2
22
Relay B Assignment
rLyb
Same selection as rLyA
0
23
Relay C Assignment
rLyC
Same selection as rLyA
0
24
Relay D Assignment
rLyd
Same selection as rLyA
0
25
Relay E Assignment
rLyE
Same selection as rLyA
0
26
Relay F Assignment
rLyF
Same selection as rLyA
0
27
Relay G Assignment
rLyg
Same selection as rLyA
0
28
Relay H Assignment
rLyH
Same selection as rLyA
0
29
Current Output A
CurA
0=Not Assigned
0
Assignment
1=Assigned to Process
Value Output-Pen 1
2=Assigned to Process
Value Output-Pen 2
30
Current Output B
Curb
Same selection as CurA
0
Assignment
31
Current Output C
CurC
Same selection as CurA
0
Assignment
32
Current Output D
Curd
Same selection as CurA
0
Assignment
33
Current Output A Range
CoAr
0=0-20 mA
1
1=4-20 mA
34
Current Output B Range
Cobr
Same selection as CoAr
1
35
Current Output C Range
CoCr
Same selection as CoAr
1
36
Current Output D Range
Codr
Same selection as CoAr
1
37
Chart Rotation Time
Crt
0.1 to 999.0 hours per
1.0
rotation
38
Pen Action on Power Up
PAPu
0=Pen(s) go to the "home"
0
position (towards chart
center) when powered up
1=Pen(s) remain in last
position prior to power down
39
Chart Operation
Coo
0=Chart continues rotating
0
in Off Mode
in the Off mode
1=Chart stops rotating while
in the Off mode
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODES SETTINGS
SETTING SETTING