Table 3-2 program mode configuration procedure – West Control Solutions MRC 7000 Recorder Manual User Manual
Page 28
28
TABLE 3-2 PROGRAM MODE CONFIGURATION PROCEDURE
Press the SCROLL key until Prog is displayed. Press the DOWN key to enter the Program
mode. Pen 1 will be displayed in the upper display. To enter the Pen 1 parameter, press the
DOWN key. To enter the Pen 2 parameter, if provided, press the Scroll key, then the DOWN
key. To enter the unit parameter, press the SCROLL key with either Pen 1 or Pen 2 displayed
until unit is displayed, then press the DOWN key. Press the SCROLL key to advance the
display through the parameter codes and their values. Use the UP and DOWN keys to adjust
the values. After adjusting a parameter, press the SCROLL key to proceed to the next
parameter. After all selections have been made, press the UP key with a parameter in the
display (not a setting) to exit the mode. For two pen instruments the parameters and values
which are applicable to Pen 1 will appear in the upper display, then the parameters and
values which are applicable to Pen 2 will appear in the lower display. Then the unit parame-
ters and values will appear in the upper display.
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODES SETTINGS
SETTING SETTING
1
Input Select
inPS
0=J T/C degrees C
1
1=J T/C degrees F
2=K T/C degrees C
3=K T/C degrees F
4=T T/C degrees C
5=T T/C degrees F
6=R T/C degrees C
7=R T/C degrees F
8=S T/C degrees C
9=S T/C degrees F
10=E T/ C degrees C
11=E T/C degrees F
12=B T/ C degrees C
13=B T/C degrees F
14=N T/ C degrees C
15=N T/C degrees F
16=C T/ C degrees C
17=C T/C degrees F
20=RTD degrees C
21=RTD degrees F
30=0 to 5 VDC / 0 to 20mA
31=1 to 5 VDC / 4 to 20mA
32=0 to 50 mVDC
33=10 to 50 mVDC
34=0 to 25 mVDC
2
Input Correction
iCor
-300 to 300 degrees/units
0
3
Alarm 1
AL1
0=None
0
(Recorder Only)
1=Process Alarm-Direct
2=Process Alarm-Reverse
Alarm 1
AL1
0=None
(Limit Only)
1=Low Limit
2=High Limit
4
Alarm 2
AL2
0=None
0
1=Process Alarm - Direct
2=Process Alarm- Reverse
5
Display Select
diSP
1=Process Value Only
1
(Limit Only)
2=Process Value/setpoint
3=Deviation Only
4=Deviation and Setpoint
5=Setpoint Only
Note: Fault detection is not
functional for 0-5V or 0-20mA Inputs