Technical data 75, Power supply 75, Technical data – West Control Solutions KS 92-1 User Manual
Page 75: Transmitter supply u, Option), Galvanic isolation, Outputs relay outputs out1...out4, Out3, 4 as universal output, Outputs out5/6 (option), Power supply

Nominal voltage
24 V DC external
Current sink (IEC 1131 type 1
)
Logic “0
”
-3...5 V
Logic “1
”
15...30 V
Current requirement
approx.. 5 mA
TRANSMITTER SUPPLY U
T
(OPTION)
Power
:
22 mA /
³ 18 V
As analog outputs OUT3 or OUT4 and trans-
mitter supply U
T
are connected to different
voltage potentials, an external galvanic connec-
tion between OUT3/4 and U
T
is not permissible
with analog outputs.
GALVANIC ISOLATION
Safety isolation
Function isolation
OUTPUTS
RELAY OUTPUTS OUT1...OUT4
Contact type
:
potential-free changeover contact
Max.contact rating
:
500 VA, 250 V, 2A at 48...62 Hz,
resistive load
Min. contact rating
:
6V, 1mA DC
Number of electical
switching cycles
:
for I = 1A/2A:
800,000 / 500,000
(at ~ 250V (resistive load)
Note:
If the relays operate external contactors, these
must be fitted with RC snubber circuits to ma-
nufacturer specifications to prevent excessive
switch-off voltage peaks.
OUT3, 4 AS UNIVERSAL OUTPUT
Galvanically isolated from the inputs.
Freely scalable resolution
:
11 bits
Current output
0/4...20 mA configurable.
Signal range:
0...approx.22mA
Max. load:
£ 500 W
Load effect:
no effect
Resolution:
£ 22 mA (0.1%)
Accuracy
£40 mA (0.2%)
Voltage output
0/2...10V configurable
Signal range:
0...11 V
Min. load:
2 k
W
Load effect:
no effect
Resolution:
£ 11 mV (0.1%)
Accuracy
£ 20 mV (0.2%)
OUT3, 4 used as transmitter supply
Output power:
22 mA /
³ 13 V
OUT3, 4 used as logic output
Load
£ 500 W
0/
£ 20 mA
Load > 500
W
0/> 13 V
OUTPUTS OUT5/6 (OPTION)
Galvanically isolated opto-coupler outputs.
Grounded load: common positive voltage.
Output rating: 18...32 VDC;
70 mA
Internal voltage drop:
1 V with I
max
Protective circuit: built-in against short circuit,
overload, reversed polarity (free-wheel diode
for relay loads).
POWER SUPPLY
Dependent of order:
AC SUPPLY
Voltage:
90...250 V AC
Frequency:
48...62 Hz
Power consumption
approx. 10 VA
UNIVERSAL SUPPLY 24 V UC
AC voltage:
20.4...26.4 V AC
Frequency:
48...62 Hz
DC voltage:
18...31 V DC class 2
Power consumption:
approx.. 10 VA
Technical data
KS 90-1 / KS 92-1
75
Process value input INP1
Mains supply
Supplementary input INP2
Optional input INP3
Digital input di1, di2
Relay OUT1
RS422/485 interface
Relay OUT2
Digital inputs di2, 3
Relay OUT3
Universal output OUT3
Relay OUT4
Universal output OUT4
Transmitter supply U
T