Othr – West Control Solutions KS 92-1 User Manual
Page 40

Configuration level
Configuration parameters
40
KS 90-1 / KS 92-1
Name
Value range Description
Default
Err.r
Reset of all error list entries
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
6
Ò - key switches
Pid.2
Switching of parameter set (Pb, ti, td)
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
I.Chg
Switching of the actual process value between Inp1 and X2
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
di.Fn
Function of digital inputs (valid for all inputs)
0
0
direct
1
inverse
2
toggle key function
fDI1
fDI2
fDI3
Forcing di1/2/3 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
othr
Name
Value range
Description
Default
bAud
Baudrate of the interface (only visible with OPTION)
2
0
2400 Baud
1
4800 Baud
2
9600 Baud
3
19200 Baud
Addr
1...247
Address on the interace (only visible with OPTION)
1
PrtY
Data parity on the interface (only visible with OPTION)
1
0
no parity (2 stop bits)
1
even parity
2
odd parity
3
no parity (1 stopbit)
dELY
0...200
Delay of response signal [ms] (only visible with OPTION)
0