Parameters 59 – West Control Solutions KS 92-1 User Manual
Page 59

g
Resetting the controller configuration to factory setting (Default) or
resetting to the customer-specific default data set
r chapter 11.1 (Page 80)
Parameter setting level
Parameters
59
KS 90-1 / KS 92-1
Name
Value range Description
Default
InL.3
-1999...9999
Input value for the lower scaling point
0
OuL.3
-1999...9999
Displayed value for the lower scaling point
0
InH.3
-1999...9999
Input value for the upper scaling point
20
OuH.3
-1999...9999
Displayed value for the upper scaling point
20
t.F3
-1999...9999
Filter time constant [s]
0
Etc.3
0...100 (°C)
32...212 (°F
External cold-junction reference temperature (external
TC)
OFF
Lim
Name
Value range Description
Default
L.1
-1999...9999
Lower limit 1
10
H.1
-1999...9999
Upper limit 1
10
HYS.1
0...9999
Hysteresis limit 1
1
dEl.1
0...9999
Alarm delay from limit value 1
0
L.2
-1999...9999
Lower limit 2
OFF
H.2
-1999...9999
Upper limit 2
OFF