Configuration 37, Out.3, Out4 – West Control Solutions KS 92-1 User Manual
Page 37

Configuration level
KS 90-1 / KS 92-1
37
Configuration parameters
Out.3
and
Out4
Name
Value range
Description
Default
O.tYP
Signal type selection OUT3
0
0
relay / logic (only visible with current/logic voltage)
1
0 ... 20 mA continuous (only visible with current/logic/voltage)
2
4 ... 20 mA continuous (only visible with current/logic/voltage)
3
0...10 V continuous (only visible with current/logic/voltage)
4
2...10 V continuous (only visible with current/logic/voltage)
5
transmitter supply (only visible without OPTION)
O.Act
MethodofoperationofoutputOUT3(onlyvisiblewhenO.TYP=0)
1
0
direct / normally open
1
inverse / normally closed
Out.0
-1999...9999
Scaling of the analog output for 0% (0/4mA or 0/2V, only
visible when O.TYP=1..5)
0
Out.1
-1999...9999
Scaling of the analog output for 100% (20mA or 10V, only
visible when O.TYP=1..5)
100
O.Src
Signal source of the analog output OUT3 (only visible
when O.TYP=1..5)
1
0
not used
1
controller output y1 (continuous)
2
controller output y2 (continuous)
3
process value
4
effective set-point Weff
5
control deviation xw (process value - set-point)
6
measured value position feedback Yp
7
measured value INP1
8
measured value INP2
9
measured value INP3
O.FAI
Failbehaviour, behaviour of the analog output, if the signal
source (
O.Src) is disturbed.
0
0
upscale
1
downscale
Y.1
Y.2
Controller output Y1/Y2 (only visible when O.TYP=0)
0
0
not active
1
active
Lim.1
Lim.2
Lim.3
Limit 1/2/3 signal (only visible when O.TYP=0)
1
0
not active
1
active
dAc.A
Valve monitoring (DAC) (only visible when O.TYP=0)
0
0
not active
1
active
LP.AL
Interruption alarm signal (LOOP) (only visible when
O.TYP=0) (Loop-Alarm)
0
0
not active
1
active