Configuration 38, Out.5, Out.6 – West Control Solutions KS 92-1 User Manual
Page 38: Logi

Configuration level
Configuration parameters
38
KS 90-1 / KS 92-1
Name
Value range
Description
Default
HC.AL
Heating current alarm signal (only visible when O.TYP=0)
0
0
not active
1
active
HC.SC
Solid state relay (SSR) short circuit signal (only visible when
O.TYP=0)
0
0
not active
1
active
FAi.1
FAi.2
FAi.3
INP1/ INP2 / INP3 error (only visible when O.TYP=0)
1
0
not active
1
active
dP.Er
PROFIBUS error
0
0
not active
1
active: Profibus trouble, no communication with this
instrument.
fOut
Forcing OUT3 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
Out.5
/
Out.6
Configuration parameters Out.2 = Out.1 except for: Default
Y.1 = 0 Y.2 = 0
g
Method of operation and usage of output
Out.1 to Out.6:
Is more than one signal chosen active as source, those signals are OR-linked.
LOGI
Name
Value range Description
Default
L_r
Local / Remote switching (Remote: adjusting of all values by
front keys is blocked)
0
0
no function (switch-over via interface is possible)
1
always active
2
DI1 switches
3
DI2 switches (basic instrument or OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
SP.2
Switching to second setpoint
SP.2
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches