Configuration level – West Control Solutions KS 92-1 User Manual
Page 41
Configuration level
KS 90-1 / KS 92-1
41
Configuration parameters
Name
Value range
Description
Default
dP.AD
0...126
Profibus address
126
bc.up
Behaviour as backup controller (see page )
0
0
No backup functionality
1
With backup functionality
O2
Entering parameter for O
2
in ppm or %
0
0
Parameter for O
2
-function in ppm
1
Parameter for O
2
-function in %
Unit
Unit
1
0
without unit
1
°C
2
°F
dP
Decimal point (max. number of digits behind the decimal point)
0
0
no digit behind the decimal point
1
1 digit behind the decimal point
2
2 digits behind the decimal point
3
3 digits behind the decimal point
LED
Function allocation of status LEDs 1 / 2 / 3 / 4
0
10
OUT1, OUT2, OUT3, OUT4
11
Heating, alarm 1, alarm 2, alarm 3
12
Heating, cooling, alarm 1, alarm 2
13
Cooling, heating, alarm 1, alarm 2
14
Bus error
dISP
0...10
Display luminosity
5
C.dEl
0..200
Modem delay [ms]
Additional delay time, before the received message is
evaluated in the Modbus. This time is required, unless
messages are transferred continuously during modem
transmission.
0
FrEq
Switching 50 Hz / 60 Hz (only visible with BlueControl!)
0
0
50 Hz
1
60 Hz
MAst
Modbus master/slave (see page ) (visible only with BlueControl
®
)
0
0
No
1
Yes
CycL
0...240
Master cycle (sec.) (see page ) (visible only with BlueControl
®
!)
120
AdrO
-32768...32767
Destination address (see page ) (visible only with BlueControl
®
!)
1100
AdrU
-32768...32767
Source address (see page ) (visible only with BlueControl
®
!)
1100
Numb
0...100
Number of data (see page ) (visible only with BlueControl
®
!)
1
ICof
Block controller off (only visible with BlueControl!)
0
0
Released
1
Blocked
IAda
Block auto tuning (only visible with BlueControl!)
0
0
Released
1
Blocked