F3 & f4 motors, F5 & f6 motors, Wiring supply, signal and feedback – Warren Controls AmurAct Actuator Linkage and Motor User Manual
Page 7
7
AmurAct
IOM_AA_RevH_0413
WIRING SUPPLy, SIGNAL AND FEEDBACk
SUPPLY VOLTAGE
Locate the green case-grounding wire inside the motor case and connect it to the earth ground lead from the
power source. Connect the neutral (typically white) wire to terminal one (1) on terminal block TB5. Connect
the “hot” (typically black) wire to terminal two (2).
1 2
TB5
Neutral
liNe
120 Vac
f3 & f4 mOTORS
120 VAC (Single-phASe 50/60 hz)
Locate the green case-grounding
wire inside the motor case and
connect it to the earth ground lead
from the power source. Connect
one “hot” wire to each of the two
terminals on terminal block TB5.
1 2
TB5
liNe
liNe
220 Vac
earth grouNd
f5 & f6 mOTORS
220 VAC (Single-phASe 50/60 hz)
1 2
TB1
CoMMoN (-)
(liNe)
24 VAc OR 30 VDc
3 4 5
If the actuator is to be powered by 24 vAC or 30 vDC, connect the negative or common wire to termi-
nal ONE (1) and the positive (or "hot" wire) to Terminal TWO (2) on TB1. When powered by (24 vDC,
Special Consideration) voltage, motor torque will be reduced by approximately 10% which will reduce
close off capability. Contact the factory for questions.
f3 & f4 mOTORS
24 VAC or 30 VDC
CONTROL SIGNAL - Current (milliamp)
If the control signal is 4 - 20 mA, connect the control wires to TB1 as shown below. Dip-
switch #3
MUST be in the ON position.
1 2
TB1
CoMMoN (-)
(+) CoNtrol 4-20 Ma dC
3 4 5
earth grouNd
(24 VDc - W / Special considerations)