beautypg.com

Warren Controls AmurAct Actuator Linkage and Motor User Manual

Page 26

background image

26

2600 Emrick Blvd • Bethlehem, PA 18020 • USA • 800-922-0085 • www.warrencontrols.com

IOM_AA_RevH_0413

NOTES

1. Linkage Model LS at factory is aligned with the pipe center line. It is specified when line media are below 250 deg. F., or

340 deg. F. when the valve body is insulated.

2. Linkage Model LE must be installed perpendicular to the pipe center line. It is specified when line media flowing through
un-insulated valves exceed 250 deg. F., or 340 deg. F. through insulated valves. The 180-degree offset anti-rotation

tailpiece must also be installed.

3. Actuators F3, F4, F5 and F6 are similar in appearance. The label on F3 & F5 states that output torque is 120 lb. in., and F4

& F6 states 240 lb. in.

4. Split-ranging, or two-stage (two valve) control can be accomplished in the linearized operating mode. Call the factory for

additional instructions.