beautypg.com

Electric actuator specifications (tr5000-x), Vms-25 bcm – Warren Controls PICV Series User Manual

Page 3

background image

3

PRESSURE INDEPENDENT CONTROL VALVE PICV_IOM_REVF_0114

DPRV DOUBLE ACTING DIAPHRAGM ACTUATOR WITH SPRING ASSIST

Control Signal:

Differential Pressure from Control Valve,

2.0 to 8 PISG (0.14 to 0.55 BARD)

150 PSIG (10.3 BARD) Max Static

Fluid:

Chilled Water Typical, Water or Water/Glycol from 35 °F- 180°F (2°C - 82°C )

Spring Pack:

Low DP Spring: Adjustable 2 to 6 PSIG (0.14-0.41 BARD)

Medium DP Spring: Adjustable 5 to 8 PSIG (0.34-0.55 BARD)

Construction:

Cast Gray Iron Class G3000, epoxy coated, epoxy coated spring, SS components, Woven Buna-N, nylon reinforced.

Temperature Limits:

Ambient 32°F - 122°F ( 0°C - 50°C )

Mounting:

Factory Aligned, Vertical Above Centerline of Control Valve

Consult factory for preconfigured alternate orientations

ELECTRIC ACTUATOR SPECIFICATIONS (TR5000-X)

Valve Usage:

5, 6, 8, & 10 inch, DN125, DN150, DN200, DN250

Control Signal:

4-20 mAdc (Factory Setting), 0-10 Vdc, 2-10 Vdc, or 0-20 mAdc; Field Selectable (Dip Switch)

Control Action:

Direct Acting, Actuator Shaft Extends on Increasing Signal (Factory Setting) or

Reverse Acting, Actuator Shaft Retracts on Increasing Signal; Field Selectable (Dip Switch)

Power

Supply: 220

VAC

Power

Consumption:

12VA

Timing:

90.68 Seconds / Inch (3.57 s/mm)

Feedback Signal:

4-20 mAdc (Factory Setting), 0-10 Vdc, 2-10 Vdc, or 0-20 mAdc

Field Selectable (Dip Switch); Feedback Signal Increase as Actuator Shaft Extends (Factory Setting) or Feedback
Signal Increases as Actuator Shaft Retracts; Field Selectable (Dip Switch)

Failure Mode:

Fail Actuator Shaft Retracted on Loss of Signal (Factory Setting) or Fail Actuator Shaft Extended on Loss of Signal

Field Selectable (Dip Switch); Actuator Shaft Fails In Last Position on Loss of Power

Manual

Override:

Yes

Construction:

Die Cast Aluminum Motor Housing & Yoke. Painted.

Case Has Two PG11 Cable Glands Accepts 0.197 to 0.394 inch (5mm to 10mm) Diameter Cable

Connections: Coded

Screw

Terminals

Locations:

NEMA Type 3 / IP54

Temperature Limits:

Ambient 14˚F to 122˚F ( -10˚C to 50˚C )

Relative Humidity:

< 95% RH (40ºC)

Mounting:

Factory Aligned, Vertical Above Centerline of Control Valve; Consult factory for preconfigured alternate orientations

4X 0.31 in (0.79 cm)

THRU MOUNTING FOOT

8.75 in (22.23 cm)

6.69

in (

16.99

cm)

6.72 in

(17.O7 cm)

4.91 in

(12.47 cm)

6.97 in

(17.7O cm)

5.19 in

(13.18 cm)

1/2 in (1.27 cm)

8.5 in (21.59 cm)

VMS-25 BCM