PRESSURE INDEPENDENT CONTROL VALVE PICV_IOM_REVF_0114

PACKING ADJUSTMENT

Series PICV packing is self-adjusting and requires no external adjustment.

MAINTENANCE

Series PICV (Pressure Independent Control Valves) are for the most part

maintenance free when properly selected and installed. Rebuilding of these valves

should not be necessary under normal operating conditions. For best operation

follow installation guidelines (See Installation); maintain the fluid pressures,

temperature, and flow within the limits of the valve (See Specification Section and

PICV Product Specification for details). In installations where high vibration exists,

electrical and sensing connections should periodically be checked for integrity.

Water should be in specification of the Warren Controls water quality guidelines.

UNDER NORMAL OPERATING CONDITIONS AND GOOD WATER QUALITY MANY YEARS OF MAINTENANCE FREE SERVICE CAN BE EXPECTED!

PICV WEIGHTS

Control Valves in HVAC Water Systems
Fluid Quality and Service Life Guide Lines

The purpose of these guidelines is to avoid valve and water systems problems caused by poor water quality in HVAC systems. While all
cooling and heating systems are susceptible to problems, closed chilled water systems, including those containing brine or glycol, are
especially prone to system and valve problems. To achieve the satisfactory operation and maximum life of your Warren Controls valve, it is
important that the following recommendations are adhered to and that a water treatment, filtration and control specialists be consulted
before the system start-up.

Weights for models with VM actuators do not include a VMS-25 BCM. Add 4.25 lbs (2kg) Actual shipping weights may vary.

MODEL

PICV SIZE

CONTROL VALVE

ACTUATOR

DPRV

ACTUATOR

TOTAL WT (LBS)

TOTAL WT (KG)

P2x23xx-E02x-P2xDx-2L

2-1/2 in, DN65

VM-1500E

2L

144.00

65.32

P2x23xx-E02x-P2xDx-2M

2-1/2 in, DN65

VM-1500E

2M

147.25

66.79

P3x23xx-E02x-P3xDx-2L

3 in, DN80

VM-1500E

2L

172.00

78.02

P3x23xx-E02x-P3xDx-2M

3 in, DN80

VM-1500E

2M

175.25

79.49

P4x23xx-E02x-P4xDx-2L

4 in, DN100

VM-1500E

2L

262.00

118.84

P4x23xx-E02x-P4xDx-2M

4 in, DN100

VM-1500E

2M

265.25

120.32

P5x23xx-E02x-P5xDx-2L

5 in, DN125

VM-5000E

2L

345.00

156.49

P5x23xx-E02x-P5xDx-2M

5 in, DN125

VM-5000E

2M

348.25

157.97

P5x23xx-TIG1-P5xDx-2L

5 in, DN125

TR5000-X

2L

335.40

152.14

P5x23xx-TIG1-P5xDx-2M

5 in, DN125

TR-5000-X

2M

338.65

153.61

P6x23xx-E02x-P6xDx-2L

6 in, DN150

VM-5000E

2L

438.00

198.68

P6x23xx-E02x-P6xDx-2M

6 in, DN150

VM-5000E

2M

441.25

200.15

P6x23xx-TIGx-P6xDx-2L

6 in, DN150

TR5000-X

2L

428.40

194.32

P6x23xx-TIGx-P6xDx-2M

6 in, DN150

TR-5000-X

2M

431.65

195.80

P8x22xx-E02x-P8xDx-2L

8 in, DN200

VM-5000E

2L

652.00

295.75

P8x22xx-E02x-P8xDx-2M

8 in, DN200

VM-5000E

2M

655.25

297.22

P8x22xx-TIG1-P8xDx-2L

8 in, DN200

TR5000-X

2L

642.40

291.39

P8x22xx-TIG1-P8xDx-2M

8 in, DN200

TR-5000-X

2M

645.65

292.86

P1x22xx-E02x-P1xDx-2L

10 in, DN250

VM-5000E

2L

945.00

428.65

P1x22xx-E02x-P1xDx-2M

10 in, DN250

VM-5000E

2M

948.25

430.12

P1x22xx-TIG1-P1xDx-2L

10 in, DN250

TR5000-X

2L

935.40

424.29

P1x22xx-TIG1-P1xDx-2M

10 in, DN250

TR-5000-X

2M

938.65

425.77

!

DANGER

Personal injury may result from uncontrolled
release of spring force. There is significant
preload on the spring in the actuator on the
differential pressure control segment (DPRV)
of the PICV. Disassembling the actuator will
release the spring force (preload) and may
cause serious personal injury.