beautypg.com

6 zero calibration, Zero calibration, Figure 8: magnetic mode selector – Spectrex Xenon 700 SIL Open-Path Gas Detection System User Manual

Page 56

background image

SafEye

TM

Xenon 700S SIL Gas Detector

44

Zero Calibration

6.6

Zero Calibration

Zero calibration must be done after:

Installation

Realignment

Window Cleaning

Any change in Detector or Source position

Precise alignment must be performed prior to the zero calibration procedure.
Zero calibration should be performed in good weather conditions with
insignificant gas concentrations in the surrounding environment or indoors.

To perform the zero calibration procedure:

1

Switch from Normal to Alignment mode indication.

2

Switch from Alignment to Standby mode.

3

Switch from Standby to Zero Calibration mode.

The 0-20mA output should now be at 1mA.

4

Wait up to 60 seconds until it switches to Normal mode. The Detector
reading is now set to normal. The 0-20mA output should now indicate
4mA.

Switching from each position (above first three instructions) can be done
by HOST HART (refer to TM888030) or RS485 (refer to TM888050 or
TM799060), or by moving the magnetic mode selector above the
magnetic switch (see Figure 8).

Figure 8: Magnetic Mode Selector