20

System Set Up

3.3.2.3 Zero Calibration

Zero Calibration can be enabled or disabled as follows:

Enable – Zero calibration is performed according to background

Disable – The Detectors are not updated due to change of background

3.3.2.4 Other Functions

Table 8: Other Functions

Function

Accessory
Relay

Accessory Relay is
activated at warning level

Accessory Relay is activated
at alarm level

Alarm

Latching

No latching function at

alarm relay

Alarm relay is latched.
Latching reset can be
performed by momentary
power disconnection or when
Detectors are set to alignment

mode

4-20 mA
mode

Continue reading of the
0-20mA per the gas
concentration level
(see Table 1)

Discrete reading of the
0-20mA output according to
the Detector status
(see Table 2)

Beam Block
During

Alarm

Non latching of alarm
indication during blocking

mode

Alarm outputs are latched
when the Detector turns to
blocking mode from alarm
position. Latching reset can be
provided only if the Detector

turn to normal mode

3.3.2.5 Address Setup

The Detector provides up to 247 addresses that can be used in RS-485
communication link.

3.3.2.6 Heated Optic Operation

The heated optics for the Detector unit can be defined as one of the
following modes:

OFF – Not operated

ON – Operated continuously

AUTO – On, per temperature change (default)

When operated per temperature change, the user can define the start
temperature below which the window will be heated between 0 to 50°C. The
Detector will stop heating the window when the temperature will be 15°C
above the defined temperature.

This feature relates to the Detector only.