7 detector wiring, Detector wiring – Spectrex Xenon 700 SIL Open-Path Gas Detection System User Manual
Page 46
SafEye
TM
Xenon 700S SIL Gas Detector
34
Detector Wiring
5.7
Detector Wiring
➣
To install the Detector wiring:
1
Remove the four (4) socket-head-screws (item 14, Figure 5) that secure
the Detector back cover (item 15, fig. 4). The chamber is now revealed.
2
Remove the protective plug mounted on the Detector conduit/cable
entry inlet; pull the wires through the Detector inlet (item 4, Figure 6).
Use a 3/4” – 14NPT or M25x1.5 explosion-proof conduit connection /
cable gland to assemble the cable / explosion-proof conduit to the
Detector.
3
Connect the wires to the required terminals (item 2, Figure 6) according
to the wiring diagram. See Detector Terminal Wiring, page 38 and
Figure 9, Figure 10,Figure 11 Appendix B.
4
Connect the grounding wire to the ground screw outside Detector
(item 3. Figure 6). The Detector must be well grounded to Earth Ground.
5
Check the wires for secure mechanical connection and press them neatly
against the terminal to prevent them from interfering while closing the
cover (item 15, Figure 5)
6
Place and secure the Detector back cover using four (4) socket-head-
screws (item 14, Figure 5)