3 operational modes, 1 operation modes, 1 normal mode – Spectrex Xenon 700 SIL Open-Path Gas Detection System User Manual
Page 27: 2 maintenance call mode (3ma output), Operational modes, Operation modes, Normal mode, Maintenance call mode (3ma output), 3operational modes
Operation Modes
15
3
Operational Modes
➣ In this chapter…
page 15
page 17
page 18
3.1
Operation Modes
The SafEye 700S has four operational modes:
Normal Mode, page 15
Maintenance Call Mode (3mA Output), page 15
Fault Mode, page 16
Zero Calibration Mode (1mA Output), page 16
3.1.1 Normal Mode
This mode is used for gas detection. In normal mode, the following statuses
are possible:
Normal: Signal received from gas detection is at safe levels
Warning: Gases have been detected at warning levels
Alarm: Gases have been detected at alarm levels
Note: For the standard 0-20mA output, the Warning and Alarm levels are
not relevant. The user chooses these alarm levels at the controller. The
output Detector will be 4mA at zero reading and 20mA for full-scale reading.
Warning and Alarm states are relevant where the stepped 0-20mA output is
used and will energize the warning and alarm relays.
If the RS485 output is used, the Detector changes its status from ‘N’ to ‘W’
at Warning level and to ‘A’ at Alarm.
3.1.2 Maintenance Call Mode (3mA Output)
This mode indicates low signal or low signal ratio that may be caused by a
dirty window; misalignment; poor source or that one of the Detectors
parameters is at the ‘limit’ value.
The Detector continues to function and reads any gas present, but provides
a (3mA) pre-warning signal that a maintenance procedure is required.