3 default detector set up, Default detector set up, Table 9: detector default set up – Spectrex Xenon 700 SIL Open-Path Gas Detection System User Manual
Page 33: Table 10: source default set-up
TM 799200 Rev (C), January 2014
System Set Up
21
The Source heated optic must be defined with the order in two options:
Heated continuously
Start heating below 41°F (5°C). (default)
3.3.3 Default Detector Set up
The Detector has 8 functions that can be programmed according to the
customer requirement at factory or at customer facility using a software
Host or a handheld unit. The standard set up is as follows:
Table 9: Detector Default Set Up
Function
Setting
Gas Type
2
Full scale sensitivity
5 LEL.m
BG Zero Calibration
Enabled
Accessory Relay
Warning*
Alarm Latching
No
0-20mA
Continuous**
Beam block during alarm
No latch
Heat mode
Auto
Heat on
5
* Only refers to wiring option with Accessory relay output
** Only refer to the wiring options with 0-20mA
Table 10: Source Default Set-Up
Function
Setting
Heat mode
Auto
Heat on
5
The Source default can be changed only at the factory.