Xenon 700S SIL Gas Detector

38

Detector Terminal Wiring

5.8

Detector Terminal Wiring

The Detector has three output wiring options in the rear, segregated, “Exde“
terminal section, with 9 Terminals, labeled 1-9.

Option 3 is the default unless otherwise specified at time of order

The following describes the function of each electrical terminal of the
Detectors for all wiring options:

Table 18: Wiring Options

Wiring
Option

Terminal Number

1

2

3

4

5

6

7

8

9

3

Figure

11

(Default)

24Vdc 0Vdc Alarm

Relay

(1)

RS-485+

(3)

RS-485-

(3)

0-20mA +

(4)

0-20mA -

(4)

RS-485

RTN

(6)

2

Figure

10

24Vdc 0Vdc Alarm

Relay

(1)

Fault Relay

(2)

Accessory Relay

(5)

not used

1

Figure 9

24Vdc 0Vdc Alarm

Relay

(1)

Fault Relay

(2)

0-20mA +

(4)

0-20mA -

(4)

not used

Notes:

1

The Alarm output is a N.O. contact relay (SPST).

The contacts are closed in Gas Alarm state.

2

The Fault output is N.C. SPST relay. The contacts are closed when the
Detector is in its normal operational condition.

3

Used for communication network as specified in Appendix B.

4

See Appendix B for more details

5

The Accessory output is N.O. (SPST) relay. The Accessory Relay may act
in parallel with the ALARM relay to activate another external device or it
may provide a warning signal, depending on Function Set Up.

6

Used as RTN to the RS-485 communication port.